The above unit price does not include cabinet and battery.
Warranty: 36 months
HIGHLIGHTS
- High efficiency reduces power waste
- Expandable multi-layer protection capability
- No input phase shift
- Remote management solution combined with peripheral devices
- Smart charging technology increases battery lifespan
- Used for Data centers, networking equipment, telecommunications, security, defense, industrial equipment, medical, automation, broadcasting, television…
TECHNICAL SPECIFICATIONS
| INPUT | |
|---|---|
| Nominal voltage | 201 ~ 478Vac (L-L); 116 ~ 276V (L-N) |
| Bypass voltage | 338 ~ 458Vac (L-L); 195 ~ 264V (L-N) |
| Number of phases | 3 phases, neutral wire and ground |
| Nominal frequency | 50/60 Hz (42 – 70 Hz) |
| Power factor | ≥ 0.99 |
| THDi | <2% linear load; <5% non-linear load |
| Generator compatible | Yes |
| OUTPUT | |
| Power | 20kVA/20kW |
| Voltage | 230/400Vac default (220/380V, 240/415V optional upon installation) |
| Number of phases | 3 phases, neutral wire and ground |
| Voltage deviation | <1% |
| Frequency | 50/60Hz |
| Power factor | 1 |
| Efficiency (Online mode) | Up to 96% |
| Efficiency (ECO mode) | Up to 99% |
| Overload capacity | 102 ~ 110%: 60 minutes; 111 ~ 125%: 10 minutes; 126 ~ 150%: 1 minute |
| Parallel operation | Up to 4 units |
| BYPASS MODE | |
| Automatic transfer to Bypass mode | Overload, UPS fault |
| Maintenance switch | Available |
| EMERGENCY POWER OFF (EPO) FUNCTION | |
| UPS Emergency Power Off (EPO) function | Optional upon request |
| BATTERY | |
| Battery voltage | 320V~607V (432V default) |
| Maximum charging current | 25A |
| Backup time | Depends on the capacity of the external battery and the load power used. |
| Battery charging time | Depends on the capacity of the external battery |
| INTERFACE | |
| Control panel | Start button / Self-test / Mute alarm / Power off button |
| Status LED display | Mains mode, battery mode, Bypass mode, load capacity, battery capacity, fault status indication. |
| Communication port | RS232, expansion slot |
| Management software | Winpower power management and automatic system shutdown software compatible with Windows, Linux, Unix, Sun |
| Transfer time | 0 ms |
| N+X parallel connection function | Allows parallel connection of up to 4 units for multi-layer redundant operation (N+X), to increase power capacity multiple times and share the load evenly. |
| OPERATING ENVIRONMENT | |
| Operating ambient temperature | 0-40°C |
| Storage temperature | -15 ~ +55°C |
| Operating ambient humidity | 5% ~ 95%, non-condensing. |
| Operating altitude | < 1000m |
| Cooling system | Air convection fan |
| STANDARDS | |
| Noise level during operation | |
| Electromagnetic field (EMS) | IEC 61000-4-2 Level 4 (ESD), IEC 61000-4-3 Level 3 (RS), IEC 61000-4-4 Level 4 (EFT), IEC 61000-4-5 Level 4 (Surge) |
| EMI electromagnetic interference safety standard | IEC62040-2, with input current ≥ 25A |
| Safety standard | IEC62040-1 |
| DIMENSIONS / WEIGHT | |
| Dimensions (W x D x H) (mm) | 330 x 668 x 521 |
| Net weight (kg) | 49 |
| Gross weight (kg) | 55 |
VN
中文 (中国)



Reviews
There are no reviews yet.