The above unit price does not include cabinet and battery.
Warranty: 36 months
– 3-phase in, 3-phase out UPS with double conversion technology, advanced processor, 3C3 PRO is ideal for backup storage for industrial equipment, information technology…
– Effective protection in the industrial sector, solutions for service industries
– Easy installation, operation, and maintenance
– High efficiency
– LCD screen provides all information related to power supply and UPS operation
– Scalability and multi-layer protection, easy for UPS repair
– Effective protection in the industrial sector
– Easy installation, operation, and maintenance
– High efficiency
– LCD screen provides all information related to power supply and UPS operation
– Scalability and multi-layer protection using a shared battery system
– Provides several peripheral connections for remote management and interaction with external circuits, creating a comprehensive power management solution
– Repair, maintenance, and on-site component replacement services at reasonable costs, with rapid troubleshooting as the top priority when equipping large-capacity UPS, and we are the unit that always meets all these requirements.
DETAILED TECHNICAL SPECIFICATIONS
| INPUT | |
|---|---|
| Rated Voltage | 380VAC (L-L) / 220 (L-N) |
| Voltage Range | 201 ~ 478VAC (L-L) / 116 ~ 276VAC (L-N) |
| Number of Phases | 3-phase (Star configuration – 4 wires + ground wire) |
| Rated Frequency | 42 ~ 72 Hz |
| Power Factor | ≥ 0.99 |
| Generator Compatibility | Yes |
| OUTPUT | |
| Capacity | 200 KVA / 180 KW |
| Voltage | 380VAC (L-L) / 220 (L-N) ± 1% |
| Number of Phases | 3-phase (Star configuration – 4 wires + ground wire) |
| Waveform | True sine wave in all grid conditions and independent of the remaining battery capacity. |
| Frequency | Synchronized with input 50/60Hz ± 4Hz or 50/60Hz ± 0.05Hz (battery mode) |
| Load Connection Type | 3-phase (Star configuration – 4 wires + ground wire) |
| Efficiency | 94% (Grid mode, battery mode) >98% (ECO mode) |
| Overload Capacity | ≥ 110% ~ 125% for 10 minutes, 125% ~ 150% for 1 minute |
| Output Power Supply | Terminal box |
| BYPASS MODE | |
| Automatic Switch to Bypass | Overload, UPS failure |
| BATTERY | |
| Battery Type | 12 VDC, sealed, maintenance-free |
| Backup Time | Depends on the capacity of the external battery – Customer’s choice based on needs and cost |
| Battery Recharge Time | Depends on the capacity of the external battery |
| INTERFACE | |
| Control Panel | LCD screen and programmable buttons |
| Status LED Display | Grid mode, battery mode, bypass mode, warning |
| Communication Ports | RS232, AS400, EPO, smart slot |
| Management Software | Winpower energy management and auto-shutdown software compatible with Windows, Linux, Unix, Sun |
| Switching Time | 0 ms |
| Emergency Power Off (EPO) Function | Yes |
| N+X Parallel Connection Function | Supports parallel connection of up to 4 units for multi-layer redundancy (N+X), capacity expansion, and load sharing. |
| OPERATING ENVIRONMENT | |
| Operating Temperature | 0 ~ 40°C |
| Operating Humidity | 20% ~ 90%, non-condensing |
| Cooling System | Air convection fan |
| STANDARDS | |
| Noise Level During Operation | 62 dB excluding alarm |
| Electromagnetic Compatibility (EMS) | IEC 61000-4-2 Level 3 (ESD) |
| IEC 61000-4-3 Level 3 (RS) | |
| IEC 61000-4-4 Level 4 (EFT) | |
| IEC 61000-4-5 Level 4 (Surge) | |
| Conducted and Radiated EMI | IEC62040-2:2005 / EN50091-2:1996, with input current ≥ 25A |
| DIMENSIONS / WEIGHT | |
| Dimensions (W x D x H) (mm) | 600 x 830 x 1876 |
| Net Weight (kg) | 457 |